An active harmonic filter (AHF) is a power electronics device connected in parallel to the mains supply. It measures the distorted current drawn by the load in real time, separates its harmonic components and, by injecting a balancing current of equal amplitude but opposite phase, brings the current on the source side closer to a sine wave.
An active harmonic filter (AHF) is a power electronics device connected in parallel to the mains supply. It measures the distorted current drawn by the load in real time, separates its harmonic components and, by injecting a balancing current of equal amplitude but opposite phase, brings the current on the source side closer to a sine wave. This reduces THDi and brings equipment overheating and the risk of resonance under control.
In facilities with an increasing number of drives, UPS units and LED loads, panel overheating, neutral current and unexpected tripping are common occurrences. Many teams attempt to explain these symptoms solely through compensation settings or cable cross-sections. However, the root cause is often distortion in the current waveform – that is, harmonics.
In this section of our blog, we explain what an active harmonic filter is, how it works, how it differs from passive filters and conventional compensation, in which installations it is genuinely required, and how its capacity should be determined based on measurements.
What is an active harmonic filter (AHF)?
An active harmonic filter is a power quality device that dynamically suppresses harmonic currents generated by non-linear loads. It is not a fixed circuit consisting of a capacitor and an inductor, but rather an intelligent current source operated by an IGBT- or SiC-based inverter.
Conventional compensation manages reactive power. The AHF, on the other hand, primarily targets distortion in the current waveform. When required, it can also provide additional functions such as reactive power support, phase imbalance correction and neutral current suppression. At Aha Teknoloji, this is the most common misconception we encounter in the field: the assumption that reactive power penalties and harmonic issues can be resolved with the same device.
AHF is used across a wide range of applications, from industrial facilities connected to industrial zones (OSB) to hospitals and data centres, and from metal processing lines to textile and plastic injection moulding lines. The common factor is a high proportion of non-linear loads, such as drives, rectifiers, UPS units or welding machines.
How does AHF work?
AHF operates via a three-step cycle: measurement, calculation and injection of an out-of-phase current. This cycle is repeated within milliseconds, which is why it maintains the filter response even if the load profile changes.
In practice, this cycle tracks disturbances even during sudden torque changes in the drive or during the UPS’s grid-to-battery switchover. This is precisely what a passive filter cannot do: automatically update its settings as frequency and amplitude vary.
Measurement and separation
High-accuracy current transformers continuously sample the load current. The digital signal processor separates the fundamental frequency component (50 Hz) from the rest of the spectrum using instantaneous power theory or FFT-like methods. Components from the 2nd to the 50th order are calculated, together with their amplitude and phase angle.
The controller generates the exact opposite of the unwanted components as a reference signal. The PWM-controlled inverter converts this signal into a real-world current and injects the balancing current into the grid via the busbar. When the load’s distorted current is combined with the AHF injection, the remaining current on the source side approaches a sine wave. The result is a reduction in THDi and the distortion at the common connection point being brought within limits.
Many AHFs can provide reactive power support and load balancing in addition to harmonic suppression. However, it is incorrect to size an AHF solely as a reactive power compensation device. If the reactive power requirement is dominant and rapid, the primary solution is often a Varmatik SVG. If harmonics are the dominant issue, the AHF takes precedence. Both can also be configured together.
What is the difference between AHF, passive filters and conventional compensation?
The three technologies address different issues. A passive filter is an LC circuit tuned to specific frequencies. Conventional compensation manages reactive power using staged capacitors. AHF, on the other hand, actively dampens a broad spectrum of variable harmonic currents.
The table below helps you quickly compare which criteria are most important when making a decision.
Comparison of AHF, passive filters and conventional compensation
| Criterion | AHF | Passive filter | Conventional compensation |
| The main objective | Harmonic current attenuation | Selective-order damping | Reactive power / cos φ |
| Response time | At the millisecond level | Fixed, frequency-dependent | Seconds, in increments |
| Load type | Variable, broad spectrum | Fixed, predictable | Slow-changing reactive |
| Risk of resonance | Low (active source) | High (mains) | It may increase with a capacitor |
| THDi effect | Strong in broadband | Limited to the adjustable range | It does not target directly |
| Modular growth | Easy (parallel unit) | Limited | Adding a level |
| Typical cost | High | Low to medium | Low |
| When to choose | Driver/UPS high-load line | Single dominant order | Reactive and punishment-focused |
The table shows that reactive power alone is not a justification for AHF. AHF becomes a key consideration when the harmonic spectrum is broad and the load profile is variable. If there is a single-order, constant source, a passive filter may still be cost-effective. The decision is always clarified by measurement.
In which facilities is an AHF required?
An AHF is required in facilities where the non-linear load ratio is high and THDi or TDD limits are exceeded. Production lines with a high density of drives, data centres with UPS systems, hospital technical infrastructure, welding and induction furnace lines, and commercial buildings with a high density of LED and SMPS systems are typical candidates.
At Aha Teknoloji, we most frequently encounter the following scenarios in the field. The compensation panel is malfunctioning frequently, the neutral conductor is overheating, transformer noise is increasing, or the OSB/grid operator is reporting limit exceedances at the PCC point. If several of these symptoms occur simultaneously, a spectrum analysis is carried out first, followed by a decision on the appropriate filter.
If you are only incurring reactive power penalties and the spectrum is clean, dynamic compensation is usually the primary solution. For fast-changing loads where a conventional panel proves inadequate, the Varmatik SVG offers a more direct solution. If both reactive power and harmonics are dominant, a hybrid configuration (SVG + AHF or existing panel + AHF) is considered. You can click here to read our article titled ‘Why Has the Lifespan of Conventional Compensation Come to an End?’.
The risk of resonance also influences the choice. At the frequency where the capacitor bank’s impedance intersects with the grid impedance, passive components can amplify distortion. In this case, AHF offers an alternative that does not feed resonance. Click here to read our article titled “What Is Resonance in Compensation?”.
5 signs to help you determine whether your facility requires an AHF
If more than one of the following five signs is present at your facility, you should take the need for an AHF seriously. A single sign is not a diagnosis, but when they occur together, a measurement plan becomes essential.
1. Panel, cable or transformer heating is higher than normal for the load, and the difference is clearly visible on a thermal camera. Click here to read our article titled ‘Why Do Panels Overheat in Factories?’.
2. The neutral current is close to the phase currents, or the neutral busbar is overheating (suspected accumulation of third-harmonic distortion).
3. Compensation contactors are switching frequently, capacitor life is short, and the power factor (cos φ) remains erratic.
4. Drives, UPS units or sensitive electronic equipment are experiencing repeated unexplained resets, faults and protection trips.
5. In power quality measurements, THDi or TDD exceeds the IEEE 519 / operator limit, and the 5th, 7th, 11th or 13th harmonics are dominant in the spectrum.
If you notice these signs, the next step is not to select a device from a catalogue, but to carry out planned measurements using a Class A or equivalent analyser. You may also wish to refer to our article, which explains in detail how to interpret these symptoms. Click here to read our article entitled ‘How to Identify Harmonic-Related Problems’.
The AHF capacity is selected in amperes based on the RMS value of the measured harmonic current. Rough guidelines, such as a percentage of the transformer’s kVA rating, are not sufficient on their own. The correct approach is to calculate the harmonic current based on the fundamental current and THDi (or order-by-order spectrum), derive the target distortion level, and allow for a safety margin.
Approximate calculation of harmonic current
The total harmonic current is roughly expressed as: Ih ≈ I1 × THDi. Here, I1 is the RMS value of the fundamental frequency current, and THDi is the total harmonic distortion of the current (expressed as a decimal). For example, if measurements show I1 = 400 A and THDi = 0.28, Ih is found to be approximately 112 A. This value represents an initial estimate of the minimum harmonic current budget that the filter must meet.
A more precise spectrum is used. The currents of each order are summed in square form: Ih = √(I2² + I3² + … + I50²). In a three-phase, four-wire system, third-harmonic currents are summed at the neutral point. If neutral suppression is required, the four-wire AHF and neutral injection capacity are also checked.
Target deviation and safety margin
It is not always necessary for the filter to reduce all Ih to zero. The aim is to bring the TDD/THD down to the level specified by IEEE 519 or the operator. In practice, the required balancing current is estimated using the approximation Icomp ≈ √(Ih_measured² − Ih_target²). A margin of typically 20 per cent to 30 per cent is added to this value to account for temperature derating, future load increases and measurement uncertainty.
Example logic (not based on actual site data, but to illustrate the method): Let the measured Ih be 112 A and the Ih remaining within the target band be 40 A; then Icomp ≈ √(112² − 40²) ≈ 105 A. With a 25 per cent margin, the AHF rated current to be selected would be approximately 130 A. The actual selection must always be based on the on-site spectrum and the CT ratio.
Why actual measurement is essential
The ‘facility kVA × fixed percentage’ formulas found in catalogues ignore load variability and shift differences. Without a one-week measurement campaign representing the actual load, the selected AHF will either be insufficient or unnecessarily oversized. At Aha Teknoloji, we always base our sizing on measurement data and the load spectrum. This is where the difference between a manufacturer and an integrator becomes apparent. You can click here to read our article titled ‘The Difference Between Manufacturers in Power Quality Solutions’.
Even a correctly selected AHF may prove ineffective in the field if the CT orientation is incorrect or cooling is inadequate. The quality of the installation is just as crucial as the device’s capacity.
In closed-loop control, current transformers are generally positioned on the source side, so that they can also monitor the AHF injection point. If the CT polarity is reversed, the filter will amplify the distortion. Class 0.5s or better accuracy, a non-saturating ratio and short secondary cabling are fundamental rules.
The connection topology can be centralised (main distribution) or at the load point (critical line). Centralised installation benefits from load diversity and is cost-effective. On sensitive circuits, point-of-use installation eliminates cable heating at source. If a capacitor bank is present, a detuning reactor or LCL output filter must be checked to ensure that the switching ripple at the AHF output does not induce resonance.
Cooling and derating must not be overlooked. Internal cabinet temperature, altitude and side-by-side module placement reduce the rated current. In modular units, communication for parallel operation, master-slave synchronisation and fault backup must be specified in the commissioning protocol.
Before commissioning is complete, open and closed-loop spectrum recording, protection coordination and remote monitoring (Modbus, Ethernet) must be included in the checklist. Otherwise, the warranty process and site acceptance will be incomplete.
IEEE 519-2022 defines harmonic control at the point of common connection (PCC). The equipment terminal is not the PCC. THD limits for voltage distortion are graded according to busbar voltage. For example, 8 per cent for 1 kV and below, and 5 per cent for the 1 kV to 69 kV range are typical upper limits. On the current side, TDD is used. TDD relates the harmonic current not to the instantaneous load, but to the maximum demand current (IL). This ensures that no unfair penalties are imposed due to artificially inflated THDi at low loads.
Compliance cannot be demonstrated by a single instantaneous measurement. The standard is based on a campaign lasting at least one week and statistical percentiles. Daily 99 per cent very short-term values are evaluated alongside weekly 95 per cent and 99 per cent 10-minute values. Compliance of the measuring instrument with IEC 61000-4-30 Class A is critical for comparable data. IEC TR 61000-3-6 serves as a guide for emission allocation in medium-voltage connections.
During site acceptance, the spectrum before and after the AHF, as well as the TDD/THD at the PCC, neutral current and switchboard temperature, must be compared under the same conditions. The ‘on and off’ filter test quantifies the actual gain. If there is no exceedance of limits, it is sound engineering practice not to invest in an AHF.
In Turkey, industrial estates (OSB) and distribution companies frequently refer to IEEE 519. The limit specified in the contract applies to the point of connection (PCC). Therefore, assuming the measurement point is the panel input undermines the compliance report from the outset.
An active harmonic filter is a power quality solution that dynamically attenuates harmonic current in modern installations. It differs from a passive filter in its wide frequency range and adaptability to variable loads. The key difference from conventional compensation, however, is that its primary objective is not to avoid reactive power penalties, but to address waveform distortion.
The answer to the question of whether it is truly necessary for your facility lies not in the catalogue, but in the measurements. Panel heating, neutral current, the spectrum and IEEE 519 / operator limits must all be considered together. The unit is selected in amperes based on capacity, Ih and the target distortion level. A safety margin is included, and the CT and cooling are correctly configured.
At Aha Teknoloji, we manufacture AHF and Varmatik SVG units using in-house engineering, and base our selection on on-site measurements. If you wish to clarify matters without any sales pressure, you can request a measurement and preliminary assessment for your facility.
1) What is the most significant difference between an active harmonic filter and a passive filter?
A passive filter is a fixed LC circuit tuned to specific frequencies. An AHF, on the other hand, is an active source that measures and injects current in the opposite phase; it has a broad frequency spectrum and adapts to varying loads. The risk of resonance is much lower with an AHF.
2) Does an AHF resolve reactive power penalties on its own?
No. The primary function of an AHF is to address harmonic current. Whilst some models may also provide reactive power support, the primary solution for rapid and significant reactive power requirements is generally an SVG or a properly configured compensation system.
3) How is the AHF capacity selected?
The measured RMS value of the harmonic current (Ih ≈ I1 × THDi or the sum of the spectrum) is taken as the basis. The required Icomp is calculated to meet the target TDD/THD band, after which a margin of 20 to 30 per cent is added to account for temperature and growth. The transformer kVA percentage alone is not sufficient.
4) Where and how is compliance with IEEE 519 demonstrated?
Compliance is demonstrated at the PCC, preferably through a one-week measurement campaign using statistical percentiles. The device terminal does not substitute for the PCC. TDD is used on the current side, and THD on the voltage side.
5) When should an AHF be preferred, and when an SVG?
AHF should be used if THDi/TDD and spectrum distortion are predominant. Varmatik SVG should be used if reactive power and cos φ fluctuations are predominant. If both are present, a hybrid configuration should be considered. The decision must be based on the measurement data.